Children’s Medical Center: Cooling Tower Treatment System

Project:

Children’s Medical Center

Location: Plano, TX
EasyWater Rep: Texas Air Systems
Scope of Work:

(3) 890 Ton Cooling Towers

EasyWater Equipment:

Model CTF-500-S Skid Mounted Treatment System

Cooling Tower Water Treatment for Children's Medical Center in Texas
The Children’s Medical Center in Plano, Texas, recently undertook a comprehensive renovation of their Central Energy Plant (CEP) to enhance the efficiency and reliability of their cooling systems. A critical component of this upgrade was the installation of EasyWater’s CTF-500-S cooling tower water treatment system, designed to improve water quality in the cooling towers.

Problem

 

During the renovation of the CEP, the (3) 890 ton cooling towers at the Children’s Medical Center accumulated significant debris, including dust, pollen, and construction materials. This led to several issues:

  • Reduced Heat Transfer Efficiency: Deposits on heat exchange surfaces impeded heat transfer, reducing the overall efficiency of the cooling system.
  • Increased Maintenance Requirements: The presence of debris necessitated frequent cleaning and maintenance, leading to increased operational costs and downtime.
  • Health and Safety Concerns: Sediment and debris in cooling tower systems can harbor harmful bacteria, such as Legionella, posing serious health risks to patients and staff.

A separator had been used in the past for filtration, but it failed to maintain the required water clarity and system cleanliness.

Cooling Tower Basins - Before Water Treatment

Inside one of the cooling tower basins
before the CTF System was turned on

Cooling Tower Debris - Before Water Treatment

Cooling tower debris being removed
during startup

Solution

To address these challenges, the decision was made to install the CTF-500-S treatment system, a state-of-the-art solution specifically designed for cooling tower applications. The CTF-500-S treatment system incorporates several advanced features:

  1. SedimentShield Sub-Micron Filtration: Utilizes proprietary media capable of removing particles and bacteria down to sub-micron levels, significantly reducing turbidity and microbial presence in the water.
  2. Ultraviolet (UV) Sanitization: Employs UV light to effectively kill bacteria on contact, minimizing the need for chemical biocides and reducing corrosion rates.
  3. No-Salt Conditioners: Prevent and remove hard water scale deposits and biofilm, enhancing heat transfer efficiency and reducing the risk of bacterial growth.
Cooling Tower Water Treatment System - CTF-500-S

EasyWater Model CTF-500-S System for Children’s Medical Center in Plano, TX

RESULTS

 

Since the installation of the CTF-500-S treatment system, the Children’s Medical Center has observed several notable improvements:

  • Enhanced Water Clarity: The SedimentShield submicron filtration resulted in significantly clearer water, cleaner sumps and lower bacteria counts.
  • Reduced Maintenance Frequency: CTF’s filtration effectiveness has decreased the need for frequent cleaning and maintenance, leading to cost savings and reduced downtime.
  • Improved Energy Efficiency: By preventing scale and biofilm formation, the system has enhanced heat transfer efficiency, contributing to lower energy consumption.
  • Health and Safety Compliance: The significant reduction in bacterial counts, which saves chemical costs and reduces the risk of Legionella, has ensured compliance with health and safety standards, safeguarding the well-being of patients and staff.
Cooling Tower Basin - 2 Weeks After Treatment

Cooling tower basin 2 weeks after CTF System
was online

Cooling Tower Basin - 1 Year After Treatment

Cooling tower basin 1 year after CTF System
was online

The implementation of the CTF-500-S treatment system at the Children’s Medical Center has successfully addressed the water quality challenges associated with cooling towers. The advanced features of the system have led to improved operational efficiency, reduced maintenance requirements, and enhanced health and safety compliance. This case study underscores the importance of selecting appropriate filtration solutions in medical facilities to maintain optimal cooling system performance and ensure a safe environment.

 

Are you looking for cooling tower water treatment for your facility?

We manufacture and offer a complete line up of industrial water treatment solutions. Please give us a call at 1-888-766-7258, or use the form below to reach out to us, so one of our experts can help you with your project.

Bacteria Dip Slide Results - Cooling Tower Water Treatment
Bacteria dip slide test results <10 CFU/mL